Battery Testing Guide
Are you looking for Stationary Lead Acid Battery Testing?
Stationary Lead Acid Battery
IEC 60896-22 is applicable to:-
- All stationary Lead-acid cells
- Monobloc batteries of the valve-regulated type
- For Float charge application: They can be permanently connected to a load and d.c. power supply.
- In a static location: not generally moved from place to place.
They are incorporated into stationary equipment or installed in the battery room.
These kinds of batteries can be used in
- Telecom
- UPS
- Utility switch
- Emergency power or similar applications
The objective of IEC 60896-22:- It specifies the methods of tests for all types and construction of valve regulated stationary Lead acid batteries and monobloc batteries.
Does not applicable :
- lead-acid cells and monobloc batteries used for vehicle engine starting applications
- solar photovoltaic energy systems
- general purpose applications
There is a list of tests performed on the batteries for safe operation characteristics, durability Characteristics & Performance Characteristics.
Safe operation characteristics
|
||
Test Clause | Measure | Purpose |
6.1 | Gas emission | To determine the emitted gas volume |
6.2 | High Current Tolerance | To verify the adequacy of current conduction
cross- sections |
6.3 | Short circuit current & d.c internal resistance | To provide data for the sizing of fuses in the
exterior circuit |
6.4 | Protection against internal ignition from external spark sources | To evaluate the adequacy of protective features |
6.5 | Protection against the ground short propensity | To evaluate the adequacy of design features |
6.6 | Content and durability of required markings | To evaluate the quality of the markings and the
the content of the information |
6.7 | Material identification | To ensure the presence of material identification
markings |
6.8 | Valve operation | To ensure the correct opening of safety valves |
6.9 | Flammability rating of materials | To verify the fire hazard class of battery materials |
6.10 | Intercell connector performance | To verify the maximum surface temperatures of
the connectors during high rate discharges |
Performance characteristics |
||
Test Clause | Measure | purpose |
6.11 | Discharge capacity | To verify the available capacities at selected
discharge rates or discharge durations. |
6.12 | Charge retention during storage | To provide storage duration data |
6.13 | Float service with daily discharges | To determine cyclic performance under float charge conditions |
6.14 | Recharge behavior | To determine the recovery of capacity or
autonomy time after a power outage |
Durability Characteristics |
||
Test Clause | Measure | purpose |
6.15 | Service life at an operating temperature of
40 °C |
To determine the operational life at elevated temperatures |
6.16 | Impact of a stress temperature of 55 °C or
60 °C |
To determine the influence of high stress
temperatures on cell or monobloc battery life |
6.17 | Abusive over-discharge | To determine the expected behavior when excess capacity is discharged |
6.18 | Thermal runaway sensitivity | To determine the expected times to establish a condition of escalating current and temperature |
6.19 | Low-temperature sensitivity | To determine the sensitivity toward damage induced by electrolyte freezing |
6.20 | Dimensional stability at elevated internal
pressure and temperature |
To determine the propensity of the cell or
monobloc battery to be deformed by internal pressure and at elevated temperature |
6.21 | Stability against mechanical abuse of units
during installation |
To determine the propensity of the cell or
monobloc battery to fracture or leak when dropped. |
If Your Buyers Demanding for Stationary Lead Acid Battery Testing – Contact Now!
Kindly send us the following Details, So that we can provide you a quotation for the same:
- Product Name, Technical Specifications, and Brochure
- Product Images
- Total Number of Samples Required: 2
Wish this blog post will be help. If you have any other questions, please feel free to contact us. ITCIndia team looking forward work with you and get better together!
Mr. Puneet Sharma | Call: 08196980555 | E-mail: [email protected]
Get Instant Quotations, Fill the Enquiry form:
Battery Testing Laboratory
ITC India NABL Accredited Laboratory Provide Battery testing service As per IEC: 60896-11, IS 1651 in India
If you have any query regarding Battery Testing and Certification. Kindly send us your testing requirements with the product technical details to submit you our testing charges.
We are waiting for your earliest reply.You can call or write us for any clarification
Puneet Sharma | +91.8196980555 | [email protected] | ITC India Pvt. Ltd
Submit Your Testing Requirements,Please fill out the Enquiry below: